Standard Task Masterä - 2” or 2½” Valve – Side Mount 6-day timer 100 psi Epoxy Lined and Coated Carbon Steel Mineral Tanks Accumaticä Brine System. Resin Polystyrene 8% DVB CL Multiple Point ABS Distributor 110V, 60Hz, 1Ø Options ASME Code Tanks 7-day timer Demand Initiation Twin configuration with timers Twin Alternating with EDRII and PW series meter Shut Off Kit (SOK) to prevent bypass during regeneration Pressure Gauge and Test Tap Kit Skid mounting 220V, 50Hz, 1Ø
Operating Conditions 25 to 100 psi S 100°F
|
|
HF Series Application Table |
|||||||||||
|
Model № |
Mineral Tank |
Capacity and Salt |
Service Flow (gpm) |
|
Minerals |
Brine System |
|||||
|
Dia. X Side Shell (in.) |
Capacity (Kilograins) |
Salt Applied (lbs) |
Contin-uous2 |
Peak3 |
Back-wash4 (gpm) |
Resin (ft3) |
Gravel (lbs) |
Dia. X Side Shell (in) |
Salt Storage (lbs) |
Brine Valve (in) |
|
|
HF-150-2 |
20x54 |
153 |
66 |
50 |
75 |
10 |
5 |
100 |
24x40 |
500 |
3/8 |
|
HF-180-2 |
20x54 |
196 |
106 |
60 |
90 |
10 |
6 |
100 |
24x50 |
580 |
3/8 |
|
HF-240-2 |
24x54 |
245 |
106 |
86 |
117 |
15 |
8 |
150 |
24x50 |
580 |
3/8 |
|
HF-300-2 |
30x60 |
293 |
106 |
107 |
134 |
25 |
10 |
250 |
24x50 |
580 |
3/8 |
|
HF-300-2 1/2 |
117 |
150 |
|||||||||
|
HF-450-2 |
30x60 |
432 |
145 |
98 |
127 |
25 |
15 |
250 |
30x50 |
900 |
1/2 |
|
HF-450-2 ½ |
112 |
142 |
|||||||||
|
HF-600-2 |
36x60 |
594 |
244 |
107 |
135 |
35 |
20 |
350 |
39x60 |
2,040 |
1/2 |
|
HF-600- 2 ½ |
119 |
152 |
|||||||||
|
HF-600S-2 ½ |
137 |
180 |
|||||||||
|
HF-750-2 |
36x72 |
731 |
244 |
104 |
130 |
35 |
25 |
350 |
39x60 |
2,040 |
1/2 |
|
HF-750-2 ½ |
116 |
150 |
|||||||||
|
HF-750S-2 ½ |
136 |
185 |
|||||||||
|
HF-900-2 |
42x72 |
837 |
274 |
115 |
147 |
50 |
30 |
500 |
42x60 |
2,370 |
1 |
|
HF-900-2 ½ |
125 |
157 |
|||||||||
|
HF-900S-2 ½ |
155 |
217 |
|||||||||
|
HF-900S-3 |
215 |
305 |
|||||||||
|
HF-900S-4F |
360 |
499 |
|||||||||
|
HF1200-2 ½ |
48x72 |
1,170 |
388 |
120 |
210 |
60 |
40 |
1,100 |
50x60 |
3,360 |
1 ¼ |
|
HF-1200S-3 |
160 |
250 |
|||||||||
|
HF-1650-2 ½ |
54x72 |
1,609 |
559 |
130 |
260 |
80 |
55 |
1,300 |
60x60 |
4,840 |
1 ¼ |
|
HF-1650S-3 |
190 |
300 |
|||||||||
|
HF-2100-2 ½ |
60x72 |
1,890 |
559 |
140 |
270 |
100 |
70 |
1,600 |
60x60 |
4,840 |
1 ¼ |
|
HF-2100S-3 |
200 |
240 |
|||||||||
|
HF-2100S-4F |
300 |
450 |
|||||||||
|
HF-2550-2 ½ |
66x72
|
2,490 |
805 |
140 |
270 |
120 |
85 |
2,100 |
72x60 |
6,970 |
1 ¼ |
|
HF-2550S-3 |
250 |
285 |
|||||||||
|
HF-2550S-4F |
285 |
500 |
|||||||||
|
HF-3000S-3 |
72x72 |
2,700 |
805 |
260 |
350 |
140 |
100 |
2,600 |
72X60 |
6,970 |
1 ¼ |
|
HF-3000S-4F |
300 |
500 |
|||||||||
|
1. Capacities are based on 20 gpg hardness at intermittent flow rates and are 95% of laboratory results. 2. Continuous flow rates are based on 10 gpm per cubic foot of mineral or a 15 psi pressure drop, whichever is less. 3. Peak flow rates are based on 15 gpm per cubic foot of mineral or a 25 psi pressure drop, whichever is less. 4. Drains must be able to dispose of water at the listed rate for up to 20 minutes. 5. Dimensions listed are actual unit height. Add at least one foot for loading mineral tanks. 6. A twin unit includes two mineral tanks and one brine tank. |
|||||||||||
102 Charbonnet Road
Duson, Louisiana 70529
Phone 337 988 2360
Fax 337 981 7922