OBJECTIVE:
To follow consistent and technically sound sizing rules in quoting softeners.
PHILOSOPHY:
There is a tendency to undersize equipment in the pursuit of lower prices.
Defensible sizing of equipment will lend credibility and will avoid
application problems.
SOFTENER SIZING:
Hardness:
Use the hardness given by the customer. Absent a measured value use
another analysis from the same aquifer or supply source. If no value is
available our standard assumption will be 10 grains per gallon or 17.1 ppm as
CaCO3 and put a disclaimer on the quotation.
Continuous or Average Flow: Use customer supplied value. If supplied
value not available use per capita or fixture unit data.
Peak Flow: Use customer supplied value. If supplied
value not available use 1.5 to 4 times the average flow. Our standard
assumption will be a peak factor of 2.0.
Total Flow: Use customer supplied value. If supplied
value not available use 8 to 16 hours per day of average flow. Our standard
assumption will be average flow for 8 hours per day.
Resin Volume: •For a simplex, choose the volume of resin to achieve a regeneration every 18
to 24 hours at the specified Total Flow . Use minimum of 16 hours. • For
a twin alternating unit, choose the volume of resin to achieve a regeneration
every 10 to 12 hours at the specified Total Flow. Use minimum of 8 hours. • Total
Flow using the actual brine applied during regeneration. For a unit with timed
brine assume 10 lb salt/ft3 or medium salt.
25/15 rule: •
Choose pipe and valve sizing to achieve less than 25 psi head loss at peak
flow. Limiting the pressure drop over the softener piping and valving to 25
psi will limit the pressure drop across the resin bed to 20 psi. (1) •
Choose pipe and valve sizing to achieve less than 15 psi head loss at average
flow.
Minimum flow: The low flow rating for a softener to prevent channeling is 1 gpm/ft3 of resin.
Flow meters: Make certain the meters will read the
minimum and the peak specified flow. If meter will not read both flows clarify
the issue with the customer and be certain to quote the flow meter range.
Multiple unit pipe sizing: •
For a twin alternating unit the piping is sized for one unit to handle all of
the flow. •
For a twin unit or alternating lead lag, the piping can be sized for each unit
to handle half of the flow. Issue a disclaimer concerning flow capacity if one
unit is out of service. •
For triplex and quad units, use no spares when sizing the system. For triplex
systems, the time between regenerations should be 8 hours. For quad units the
time between regenerations should be 6 hours. (Note each tank is regenerated
every day when system is at capacity.) Size header for peak flow and each unit
for Flow/n where n is the number of units. Use the 25/15 rule.
Brine Tanks: Our standard is to provide enough salt in storage for six (6)
regenerations. The brine draw is fixed with the 706022, 706044 and larger
brine valves. The target is 10 lb salt/ft3 of resin. Values below 7 and above
15 should be avoided although resin specifications allow 5 to 15 lb salt/ft3
of resin. Standard grid plate height is 24 inches except for the 24 x 40 tanks
which have a 16 inch grid plate and the 18 x40 which have an 11 inch grid
plate. Be cautious with triplex and quad systems as the brine tank size may
need to be increased to allow for sufficient salt storage.
References:
(1) Tom Beggs - Purolite. 06/09/05 phone conve
Water King, Inc.
S
102 Charbonnet Road
S
Duson, LA 70529
S
(337) 988-2360