MF Softener Series Specifications |
Standard product
descriptions are used in quotations and submittals. They include part
numbers so that they will be specific and tell how the system will be
built.
SX:
Simplex
SM: Simplex Metered
TS: Twin Sequential
TA: Twin Alternating
TP: Twin Parallel
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920150 |
|
Model MF-150-1 ½”-Simplex (SX) Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
1 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code
vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
1 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
1 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
1 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S1 |
- |
49 / 65 gpm per vessel |
|
Capacity: |
CAPMF150S |
- |
153,000 grains per vessel |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day
electronic timer |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
- |
* |
- |
- |
|
Dimensions (HtxDepthxWidth): |
DIMMF150S |
- |
69 ¼” x 31 ¼” x 50” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150S |
- |
859 lbs |
|
Literature: |
LITMF |
- |
CAT231, CAT315, CAT281, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
Operating Mode: |
SIMPLEX |
- |
Simplex (-SX). Simplex systems shall have regeneration initiated
by time of day or “clock time”. SX systems shall have one brine
tank, one Taskmaster IIIä control valve, one ERCt controller.
Ordering an optional shut off kit will prevent hard water bypass. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4)
per vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920150-5 |
|
Model MF-150-1 ½”-Simplex Metered (SM) Water Softener
|
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
1 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code
vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
1 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
1 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
1 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S1 |
- |
49 / 65 gpm per vessel |
|
Capacity: |
CAPMF150S |
- |
153,000 grains per vessel |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
1 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150S |
- |
69 ¼” x 31 ¼” x 50” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150S |
- |
859 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
SIMPLEX MTR |
- |
Simplex metered (-SM). Simplex metered systems shall have
regeneration initiated by gallons treated (demand). SM systems
shall have one brine tank, one Taskmaster IIIä control valve, one
ERCd controller, one PW, PWS or TM series flow meter. Regeneration
initiation and meter display shall be provided by the ERCd. This
unit will bypass hard water during regeneration. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4)
per vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920152-10 |
|
Model MF-150-1 ½”-TS Twin Sequential Water Softener
|
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code
vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
2 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150T1 |
- |
49 / 65 gpm per vessel : 98 / 130 gpm both vessels |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director
|
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
Valves: |
707150 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day
electronic timer |
|
Shut off kit: |
720088 |
2 |
1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For
MF) |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
707143-3 |
1 |
TM200 2” Turbine flow meter 2-250 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TS |
- |
Twin sequential (- TS). In twin sequential (TS) mode both
units are in service unless a unit is in regeneration. The flow
through both units is directed into a single meter. Once a
predetermined amount of water has passed through the flow meter
the ERCd initiates sequential regeneration of both units. When
regeneration of the primary tank is complete, the ERCd sends an
intiation to the ERCt on the secondary tank causing it to
regenerate. Twin sequential systems shall have two mineral tanks,
two Taskmaster IIIä control valves, one brine tank with brine
director, one ERCd controller, one ERCt controller, one PW, PWS or
TM series flow meter and two shut off kits. An advantage of the
sequential configuration is that the secondary unit can operate
independent of the primary unit. Regeneration initiation and meter
display shall be provided by the ERCd. The ERCt controls the cycle
times on the secondary vessel. For Twin Sequential, header piping
must match meter sizing. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4)
per vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920152-11 |
|
Model MF-150-1 ½”-TA Twin Alternating Water Softener
|
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code
vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
2 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S1 |
- |
49 / 65 gpm per vessel |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director
|
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
Valves: |
707150-6 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with indicator
light (slave unit) |
|
Shut off kit: |
720088 |
2 |
1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For
MF) |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
1 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TA |
- |
Twin Alternating (- TA). In twin alternating (TA) mode units
operate so that once a predetermined amount of water has passed
through the flow meter the ERCd initiates regeneration of the
exhausted unit placing its twin in service. One unit is on line
(in service) and one is either in standby or regeneration. The
ERCd demand initiated regeneration controller controls the
regeneration cycles for both of the twin alternating units in a
master slave configuration. Twin alternating systems shall have
two mineral tanks, two Taskmaster IIIä control valves, one brine
tank with brine director, one ERCd controller, one PW, PWS or TM
series flow meter and two shut off kits. Regeneration initiation
and meter display shall be provided by the ERCd. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4)
per vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920152-12 |
|
Model MF-150-1 ½”-TP Twin Parallel Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
2 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150T1 |
- |
49 / 65 gpm per vessel : 98 / 130 gpm both vessels |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director |
|
Valves: |
707150-5 |
2 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
- |
* |
- |
- |
|
Shut off kit: |
720088 |
2 |
1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For MF) |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
2 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TP |
- |
Twin Parallel (–TP) systems are demand regenerated. Each tank is
controlled independently by a separate controller (ERCd). For each
mineral vessel, the separate controllers determine if the resin in the
mineral tank is exhausted based on the volume of water treated (or
totalized flow) and then signals the cycle timer to regenerate that
particular vessel. The vessels operate independently. Simultaneous
regeneration is controlled by blocking regeneration based on time of
day. The two units operate completely independently resulting in a
truly redundant system. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
921150 |
|
Model MF-150-2”-Simplex (SX) Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
1 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
809606 |
1 |
2" & 1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
1 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
1 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S2 |
- |
50 / 75 gpm per vessel |
|
Capacity: |
CAPMF150S |
- |
153,000 grains per vessel |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day
electronic timer |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
- |
* |
- |
- |
|
Dimensions (HtxDepthxWidth): |
DIMMF150S |
- |
69 ¼” x 31 ¼” x 50” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150S |
- |
859 lbs |
|
Literature: |
LITMF |
- |
CAT231, CAT315, CAT281, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
Operating Mode: |
SIMPLEX |
- |
Simplex (-SX). Simplex systems shall have regeneration initiated by
time of day or “clock time”. SX systems shall have one brine tank, one
Taskmaster IIIä control valve, one ERCt controller. Ordering an
optional shut off kit will prevent hard water bypass. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
921150-5 |
|
Model MF-150-2"-Simplex Metered (SM) Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
1 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
809606 |
1 |
2" & 1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
1 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
1 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S2 |
- |
50 / 75 gpm per vessel |
|
Capacity: |
CAPMF150S |
- |
153,000 grains per vessel |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
1 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150S |
- |
69 ¼” x 31 ¼” x 50” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150S |
- |
859 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
SIMPLEX MTR |
- |
Simplex metered (-SM). Simplex metered systems shall have regeneration
initiated by gallons treated (demand). SM systems shall have one brine
tank, one Taskmaster IIIä control valve, one ERCd controller, one PW,
PWS or TM series flow meter. Regeneration initiation and meter display
shall be provided by the ERCd. This unit will bypass hard water during
regeneration. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
921152-10 |
|
Model MF-150-2"-TS Twin Sequential Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
809606 |
2 |
2" & 1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150T2 |
- |
50 / 75 gpm per vessel : 100 / 150 gpm both vessels |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director |
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
Valves: |
707150 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day
electronic timer |
|
Super flow kit: |
720002 |
2 |
2" Super flow kit with two DM200G cast iron diaphragm valves |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
707143-3 |
1 |
TM200 2” Turbine flow meter 2-250 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TS |
- |
Twin sequential (- TS). In twin sequential (TS) mode both units are
in service unless a unit is in regeneration. The flow through both
units is directed into a single meter. Once a predetermined amount of
water has passed through the flow meter the ERCd initiates sequential
regeneration of both units. When regeneration of the primary tank is
complete, the ERCd sends an intiation to the ERCt on the secondary
tank causing it to regenerate. Twin sequential systems shall have two
mineral tanks, two Taskmaster IIIä control valves, one brine tank with
brine director, one ERCd controller, one ERCt controller, one PW, PWS
or TM series flow meter and two shut off kits. An advantage of the
sequential configuration is that the secondary unit can operate
independent of the primary unit. Regeneration initiation and meter
display shall be provided by the ERCd. The ERCt controls the cycle
times on the secondary vessel. For Twin Sequential, header piping must
match meter sizing. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
921152-11 |
|
Model MF-150-2"-TA Twin Alternating Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
809606 |
2 |
2" & 1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150S2 |
- |
50 / 75 gpm per vessel |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director |
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
Valves: |
707150-6 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with indicator light
(slave unit) |
|
Super flow kit: |
720002 |
2 |
2" Super flow kit with two DM200G cast iron diaphragm valves |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
1 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TA |
- |
Twin Alternating (- TA). In twin alternating (TA) mode units operate
so that once a predetermined amount of water has passed through the
flow meter the ERCd initiates regeneration of the exhausted unit
placing its twin in service. One unit is on line (in service) and one
is either in standby or regeneration. The ERCd demand initiated
regeneration controller controls the regeneration cycles for both of
the twin alternating units in a master slave configuration. Twin
alternating systems shall have two mineral tanks, two Taskmaster IIIä
control valves, one brine tank with brine director, one ERCd
controller, one PW, PWS or TM series flow meter and two shut off kits.
Regeneration initiation and meter display shall be provided by the
ERCd. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
921152-12 |
|
Model MF-150-2"-TP Twin Parallel Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100123-LC |
2 |
20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
2 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
2 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
809606 |
2 |
2" & 1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW10 |
2 |
10 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479922 |
2 |
5 ft³ / 100 lb per vessel |
|
Rated continuous / peak flow: |
QMF150T2 |
- |
50 / 75 gpm per vessel : 100 / 150 gpm both vessels |
|
Capacity: |
CAPMF150T |
- |
153,000 grains per vessel : 306,000 grains both vessels |
|
Brine Tank: |
805076 |
1 |
24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Director Assembly: |
200442-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director |
|
Valves: |
707150-5 |
2 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
- |
* |
- |
- |
|
Super flow kit: |
720002 |
2 |
2" Super flow kit with two DM200G cast iron diaphragm valves |
|
Tank Adaptor: |
720216 |
2 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
2 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF150T |
- |
69 ¼” x 31 ¼” x 76” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF150T |
- |
1661 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
TP |
- |
Twin Parallel (–TP) systems are demand regenerated. Each tank is
controlled independently by a separate controller (ERCd). For each
mineral vessel, the separate controllers determine if the resin in the
mineral tank is exhausted based on the volume of water treated (or
totalized flow) and then signals the cycle timer to regenerate that
particular vessel. The vessels operate independently. Simultaneous
regeneration is controlled by blocking regeneration based on time of
day. The two units operate completely independently resulting in a
truly redundant system. |
|
Optional PG & test tap kit: |
PGTTK |
2 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920240 |
|
Model MF-240-1 ½”-Simplex (SX) Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100124-LC |
1 |
24x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
1 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW15 |
1 |
15 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479926 |
1 |
8 ft³ / 150 lb per vessel |
|
Rated continuous / peak flow: |
QMF240S1 |
- |
51 / 67 gpm per vessel |
|
Capacity: |
CAPMF240S |
- |
245,000 grains per vessel |
|
Brine Tank: |
805077 |
1 |
24X50 Accumatic™ Brine System 21" Grid Ht
Preset Brine Draw: 91 lbs Salt Storage 640 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day
electronic timer |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
- |
* |
- |
- |
|
Dimensions (HtxDepthxWidth): |
DIMMF240S |
- |
70 1/2” x 35 ¼” x 54” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF240S |
- |
1111 lbs |
|
Literature: |
LITMF |
- |
CAT231, CAT315, CAT281, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
Operating Mode: |
SIMPLEX |
- |
Simplex (-SX). Simplex systems shall have regeneration initiated by
time of day or “clock time”. SX systems shall have one brine tank, one
Taskmaster IIIä control valve, one ERCt controller. Ordering an
optional shut off kit will prevent hard water bypass. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920240-5 |
|
Model MF-240-1 ½”-Simplex Metered (SM) Water Softener |
|
|
|
|
|
|
Mineral Tank: |
100124-LC |
1 |
24x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels |
|
Upper distributor: |
100341 |
1 |
2" Single point upper SCH80PVC |
|
Lower distributor: |
500000-1 |
1 |
Two point - 2" lower SCH80PVC |
|
Face Piping: |
806603 |
1 |
1 ½” NPT and grooved galvanized face piping |
|
Backwash Rate: |
BW15 |
1 |
15 gpm internal BW control
with 3/4" drain |
|
Media (Resin / gravel): |
479926 |
1 |
8 ft³ / 150 lb per vessel |
|
Rated continuous / peak flow: |
QMF240S1 |
- |
51 / 67 gpm per vessel |
|
Capacity: |
CAPMF240S |
- |
245,000 grains per vessel |
|
Brine Tank: |
805077 |
1 |
24X50 Accumatic™ Brine System 21" Grid Ht
Preset Brine Draw: 91 lbs Salt Storage 640 lbs |
|
Brine Valve: |
706022 |
1 |
⅜” Brine Valve |
|
Brine Line Assembly: |
200126-2 |
1 |
½” Poly Propylene Tubing for ⅜” Brine Valve |
|
Valves: |
707150-5 |
1 |
Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand
regeneration control |
|
- |
* |
- |
- |
|
Bypass: |
BYPASS |
- |
Unit will bypass hard water during regeneration |
|
Tank Adaptor: |
720216 |
1 |
Taskmaster III Side Mount SS Tank Adaptor |
|
Flow Meter: |
500841 |
1 |
PW150 1 ½” Paddle Wheel Flow Meter 5-140 gpm |
|
Dimensions (HtxDepthxWidth): |
DIMMF240S |
- |
70 1/2” x 35 ¼” x 54” |
|
- |
ADD |
- |
Add one foot to height for loading media. |
|
Shipping Weight: |
WTMF240S |
- |
1111 lbs |
|
Literature: |
LITMFMTR |
- |
CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401 |
|
Conditions: |
OPCOND |
- |
Max Operating Temp: 120F Max Operating Pressure: 125 psi |
|
- |
* |
- |
- |
|
- |
SIMPLEX MTR |
- |
Simplex metered (-SM). Simplex metered systems shall have regeneration
initiated by gallons treated (demand). SM systems shall have one brine
tank, one Taskmaster IIIä control valve, one ERCd controller, one PW,
PWS or TM series flow meter. Regeneration initiation and meter display
shall be provided by the ERCd. This unit will bypass hard water during
regeneration. |
|
Optional PG & test tap kit: |
PGTTK |
1 |
Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per
vessel |
|
BACK
TO TOP |
Part No |
Quant |
Description |
|
System: |
920242-10 |
|
| |