Delivering Experience, Quality, and Service since 1934.


       
 

HOME - Water Softeners - MF Series Softeners - Specifications

 
 

MF Softener Series Specifications

Standard product descriptions are used in quotations and submittals. They include part numbers so that they will be specific and tell how the system will be built.

SX:  Simplex
SM:  Simplex Metered
TS:  Twin Sequential
TA:  Twin Alternating
TP:  Twin Parallel

Model Pipe Size

Configuration

150 1 1/2" SX SM TS TA TP
150 2" SX SM TS TA TP
240 1 1/2" SX SM TS TA TP
240 2" SX SM TS TA TP
300 1 1/2" SX SM TS TA TP
300 2" SX SM TS TA TP
300 3" SX SM TS TA TP
450 1 1/2" SX SM TS TA TP
450 2" SX SM TS TA TP
450 3" SX SM TS TA TP
600 1 1/2" SX SM TS TA TP
600 2" SX SM TS TA TP
600 3" SX SM TS TA TP
750 2" SX SM TS TA TP
750 3" SX SM TS TA TP
900 2" SX SM TS TA TP
900 3" SX SM TS TA TP
1200 2" SX SM TS TA TP
1200 3" SX SM TS TA TP


 BACK TO TOP

Part No

Quant

Description

System:

920150

 

Model MF-150-1 ½”-Simplex (SX) Water Softener

 

 

 

 

Mineral Tank:

100123-LC

1

20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels

Upper distributor:

100341

1

2" Single point upper SCH80PVC

Lower distributor:

500000-1

1

Two point - 2" lower SCH80PVC

Face Piping:

806603

1

1 ½” NPT and grooved galvanized face piping

Backwash Rate:

BW10

1

10 gpm internal BW control
with 3/4" drain

Media (Resin / gravel):

479922

1

5 ft³ / 100 lb  per vessel

Rated continuous /  peak flow:

QMF150S1

-

49 / 65 gpm per vessel

Capacity:

CAPMF150S

-

153,000 grains per vessel

Brine Tank:

805076

1

24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs

Brine Valve:

706022

1

⅜” Brine Valve

Brine Line Assembly:

200126-2

1

½” Poly Propylene Tubing for ⅜” Brine Valve

Valves: 

707150

1

Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day electronic timer

-

*

-

-

Bypass:

BYPASS

-

Unit will bypass hard water during regeneration

Tank Adaptor:

720216

1

Taskmaster III Side Mount SS Tank Adaptor

-

*

-

-

Dimensions (HtxDepthxWidth):

DIMMF150S

-

69 ¼” x 31 ¼” x 50”

-

ADD

-

Add one foot to height for loading media.

Shipping Weight:

WTMF150S

-

859 lbs

Literature:

LITMF

-

CAT231, CAT315, CAT281, CAT610, O&M No 900401

Conditions:

OPCOND

-

Max Operating Temp: 120F Max Operating Pressure: 125 psi

-

*

-

-

Operating Mode:

SIMPLEX

-

Simplex (-SX). Simplex systems shall have regeneration initiated by time of day or “clock time”. SX systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCt controller. Ordering an optional shut off kit will prevent hard water bypass.

Optional PG & test tap kit:

PGTTK

1

Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

  

 BACK TO TOP

Part No

Quant

Description

System:

920150-5

 

Model MF-150-1 ½”-Simplex Metered (SM) Water Softener

 

 

 

 

Mineral Tank:

100123-LC

1

20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels

Upper distributor:

100341

1

2" Single point upper SCH80PVC

Lower distributor:

500000-1

1

Two point - 2" lower SCH80PVC

Face Piping:

806603

1

1 ½” NPT and grooved galvanized face piping

Backwash Rate:

BW10

1

10 gpm internal BW control
with 3/4" drain

Media (Resin / gravel):

479922

1

5 ft³ / 100 lb  per vessel

Rated continuous /  peak flow:

QMF150S1

-

49 / 65 gpm per vessel

Capacity:

CAPMF150S

-

153,000 grains per vessel

Brine Tank:

805076

1

24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs

Brine Valve:

706022

1

⅜” Brine Valve

Brine Line Assembly:

200126-2

1

½” Poly Propylene Tubing for ⅜” Brine Valve

Valves: 

707150-5

1

Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control

-

*

-

-

Bypass:

BYPASS

-

Unit will bypass hard water during regeneration

Tank Adaptor:

720216

1

Taskmaster III Side Mount SS Tank Adaptor

Flow Meter:

500841

1

 PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm

Dimensions (HtxDepthxWidth):

DIMMF150S

-

69 ¼” x 31 ¼” x 50”

-

ADD

-

Add one foot to height for loading media.

Shipping Weight:

WTMF150S

-

859 lbs

Literature:

LITMFMTR

-

CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401

Conditions:

OPCOND

-

Max Operating Temp: 120F Max Operating Pressure: 125 psi

-

*

-

-

-

SIMPLEX MTR

-

Simplex metered (-SM). Simplex metered systems shall have regeneration initiated by gallons treated (demand). SM systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCd controller, one PW, PWS or TM series flow meter. Regeneration initiation and meter display shall be provided by the ERCd. This unit will bypass hard water during regeneration.

Optional PG & test tap kit:

PGTTK

1

Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

   

 BACK TO TOP

Part No

Quant

Description

System:

920152-10

 

Model MF-150-1 ½”-TS Twin Sequential Water Softener

 

 

 

 

Mineral Tank:

100123-LC

2

20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels

Upper distributor:

100341

2

2" Single point upper SCH80PVC

Lower distributor:

500000-1

2

Two point - 2" lower SCH80PVC

Face Piping:

806603

2

1 ½” NPT and grooved galvanized face piping

Backwash Rate:

BW10

2

10 gpm internal BW control
with 3/4" drain

Media (Resin / gravel):

479922

2

5 ft³ / 100 lb  per vessel

Rated continuous /  peak flow:

QMF150T1

-

49 / 65 gpm per vessel  :  98 / 130 gpm both vessels

Capacity:

CAPMF150T

-

153,000 grains per vessel : 306,000 grains both vessels

Brine Tank:

805076

1

24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs

Brine Valve:

706022

1

⅜” Brine Valve

Brine Director Assembly:

200442-2

1

½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director

Valves: 

707150-5

1

Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control

Valves: 

707150

1

Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day electronic timer

Shut off kit:

720088

2

1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For MF)

Tank Adaptor:

720216

2

Taskmaster III Side Mount SS Tank Adaptor

Flow Meter:

707143-3

1

TM200 2” Turbine flow meter 2-250 gpm

Dimensions (HtxDepthxWidth):

DIMMF150T

-

69 ¼” x 31 ¼” x 76”

-

ADD

-

Add one foot to height for loading media.

Shipping Weight:

WTMF150T

-

1661 lbs

Literature:

LITMFMTR

-

CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401

Conditions:

OPCOND

-

Max Operating Temp: 120F Max Operating Pressure: 125 psi

-

*

-

-

-

TS

-

Twin sequential (- TS).  In twin sequential (TS) mode both units are in service unless a unit is in regeneration. The flow through both units is directed into a single meter. Once a predetermined amount of water has passed through the flow meter the ERCd initiates sequential regeneration of both units. When regeneration of the primary tank is complete, the ERCd sends an intiation to the ERCt on the secondary tank causing it to regenerate. Twin sequential systems shall have two mineral tanks, two Taskmaster IIIä control valves, one brine tank with brine director, one ERCd controller, one ERCt controller, one PW, PWS or TM series flow meter and two shut off kits. An advantage of the sequential configuration is that the secondary unit can operate independent of the primary unit. Regeneration initiation and meter display shall be provided by the ERCd. The ERCt controls the cycle times on the secondary vessel. For Twin Sequential, header piping must match meter sizing.

Optional PG & test tap kit:

PGTTK

2

Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 BACK TO TOP

Part No

Quant

Description

System:

920152-11

 

Model MF-150-1 ½”-TA Twin Alternating Water Softener

 

 

 

 

Mineral Tank:

100123-LC

2

20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels

Upper distributor:

100341

2

2" Single point upper SCH80PVC

Lower distributor:

500000-1

2

Two point - 2" lower SCH80PVC

Face Piping:

806603

2

1 ½” NPT and grooved galvanized face piping

Backwash Rate:

BW10

2

10 gpm internal BW control
with 3/4" drain

Media (Resin / gravel):

479922

2

5 ft³ / 100 lb  per vessel

Rated continuous /  peak flow:

QMF150S1

-

49 / 65 gpm per vessel

Capacity:

CAPMF150T

-

153,000 grains per vessel : 306,000 grains both vessels

Brine Tank:

805076

1

24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs

Brine Valve:

706022

1

⅜” Brine Valve

Brine Director Assembly:

200442-2

1

½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director

Valves: 

707150-5

1

Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control

Valves: 

707150-6

1

Task Master III™ 1 1/2" or 2" SS Control Valve with indicator light (slave unit)

Shut off kit:

720088

2

1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For MF)

Tank Adaptor:

720216

2

Taskmaster III Side Mount SS Tank Adaptor

Flow Meter:

500841

1

 PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm

Dimensions (HtxDepthxWidth):

DIMMF150T

-

69 ¼” x 31 ¼” x 76”

-

ADD

-

Add one foot to height for loading media.

Shipping Weight:

WTMF150T

-

1661 lbs

Literature:

LITMFMTR

-

CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401

Conditions:

OPCOND

-

Max Operating Temp: 120F Max Operating Pressure: 125 psi

-

*

-

-

-

TA

-

Twin Alternating (- TA).  In twin alternating (TA) mode units operate so that once a predetermined amount of water has passed through the flow meter the ERCd initiates regeneration of the exhausted unit placing its twin in service. One unit is on line (in service) and one is either in standby or regeneration. The ERCd demand initiated regeneration controller controls the regeneration cycles for both of the twin alternating units in a master slave configuration. Twin alternating systems shall have two mineral tanks, two Taskmaster IIIä control valves, one brine tank with brine director, one ERCd controller, one PW, PWS or TM series flow meter and two shut off kits. Regeneration initiation and meter display shall be provided by the ERCd.

Optional PG & test tap kit:

PGTTK

2

Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 920152-12   Model MF-150-1 ½”-TP Twin Parallel Water Softener 
       
Mineral Tank:  100123-LC 2 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 2 2" Single point upper SCH80PVC
Lower distributor: 500000-1 2 Two point - 2" lower SCH80PVC
Face Piping: 806603 2 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 2 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 2 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150T1 - 49 / 65 gpm per vessel  :  98 / 130 gpm both vessels
Capacity: CAPMF150T - 153,000 grains per vessel : 306,000 grains both vessels
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Director Assembly: 200442-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director 
Valves:   707150-5 2 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
- * - -
Shut off kit: 720088 2 1 1/2" Shut off kit with one DM150 cast iron diaphragm valve (For MF)
Tank Adaptor: 720216 2 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 500841 2  PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm
Dimensions (HtxDepthxWidth):  DIMMF150T - 69 ¼” x 31 ¼” x 76” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150T - 1661 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- TP - Twin Parallel (–TP) systems are demand regenerated. Each tank is controlled independently by a separate controller (ERCd). For each mineral vessel, the separate controllers determine if the resin in the mineral tank is exhausted based on the volume of water treated (or totalized flow) and then signals the cycle timer to regenerate that particular vessel. The vessels operate independently. Simultaneous regeneration is controlled by blocking regeneration based on time of day. The two units operate completely independently resulting in a truly redundant system. 
Optional PG & test tap kit: PGTTK 2 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 921150   Model MF-150-2”-Simplex (SX) Water Softener 
       
Mineral Tank:  100123-LC 1 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 1 2" Single point upper SCH80PVC
Lower distributor: 500000-1 1 Two point - 2" lower SCH80PVC
Face Piping: 809606 1 2" & 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 1 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 1 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150S2 - 50 / 75 gpm per vessel 
Capacity: CAPMF150S - 153,000 grains per vessel
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Line Assembly: 200126-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 
Valves:   707150 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day electronic timer 
- * - -
Bypass: BYPASS - Unit will bypass hard water during regeneration
Tank Adaptor: 720216 1 Taskmaster III Side Mount SS Tank Adaptor
- * - -
Dimensions (HtxDepthxWidth):  DIMMF150S - 69 ¼” x 31 ¼” x 50” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150S - 859 lbs
Literature: LITMF - CAT231, CAT315, CAT281, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
Operating Mode: SIMPLEX - Simplex (-SX). Simplex systems shall have regeneration initiated by time of day or “clock time”. SX systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCt controller. Ordering an optional shut off kit will prevent hard water bypass.
Optional PG & test tap kit: PGTTK 1 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 921150-5   Model MF-150-2"-Simplex Metered (SM) Water Softener 
       
Mineral Tank:  100123-LC 1 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 1 2" Single point upper SCH80PVC
Lower distributor: 500000-1 1 Two point - 2" lower SCH80PVC
Face Piping: 809606 1 2" & 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 1 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 1 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150S2 - 50 / 75 gpm per vessel 
Capacity: CAPMF150S - 153,000 grains per vessel
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Line Assembly: 200126-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 
Valves:   707150-5 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
- * - -
Bypass: BYPASS - Unit will bypass hard water during regeneration
Tank Adaptor: 720216 1 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 500841 1  PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm
Dimensions (HtxDepthxWidth):  DIMMF150S - 69 ¼” x 31 ¼” x 50” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150S - 859 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- SIMPLEX MTR - Simplex metered (-SM). Simplex metered systems shall have regeneration initiated by gallons treated (demand). SM systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCd controller, one PW, PWS or TM series flow meter. Regeneration initiation and meter display shall be provided by the ERCd. This unit will bypass hard water during regeneration.
Optional PG & test tap kit: PGTTK 1 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 921152-10   Model MF-150-2"-TS Twin Sequential Water Softener 
       
Mineral Tank:  100123-LC 2 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 2 2" Single point upper SCH80PVC
Lower distributor: 500000-1 2 Two point - 2" lower SCH80PVC
Face Piping: 809606 2 2" & 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 2 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 2 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150T2 - 50 / 75 gpm per vessel  :  100 / 150 gpm both vessels
Capacity: CAPMF150T - 153,000 grains per vessel : 306,000 grains both vessels
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Director Assembly: 200442-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director 
Valves:   707150-5 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
Valves:   707150 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day electronic timer 
Super flow kit: 720002 2 2" Super flow kit with two DM200G cast iron diaphragm valves
Tank Adaptor: 720216 2 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 707143-3 1 TM200 2” Turbine flow meter 2-250 gpm
Dimensions (HtxDepthxWidth):  DIMMF150T - 69 ¼” x 31 ¼” x 76” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150T - 1661 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- TS - Twin sequential (- TS).  In twin sequential (TS) mode both units are in service unless a unit is in regeneration. The flow through both units is directed into a single meter. Once a predetermined amount of water has passed through the flow meter the ERCd initiates sequential regeneration of both units. When regeneration of the primary tank is complete, the ERCd sends an intiation to the ERCt on the secondary tank causing it to regenerate. Twin sequential systems shall have two mineral tanks, two Taskmaster IIIä control valves, one brine tank with brine director, one ERCd controller, one ERCt controller, one PW, PWS or TM series flow meter and two shut off kits. An advantage of the sequential configuration is that the secondary unit can operate independent of the primary unit. Regeneration initiation and meter display shall be provided by the ERCd. The ERCt controls the cycle times on the secondary vessel. For Twin Sequential, header piping must match meter sizing.
Optional PG & test tap kit: PGTTK 2 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 921152-11   Model MF-150-2"-TA Twin Alternating Water Softener 
       
Mineral Tank:  100123-LC 2 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 2 2" Single point upper SCH80PVC
Lower distributor: 500000-1 2 Two point - 2" lower SCH80PVC
Face Piping: 809606 2 2" & 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 2 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 2 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150S2 - 50 / 75 gpm per vessel 
Capacity: CAPMF150T - 153,000 grains per vessel : 306,000 grains both vessels
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Director Assembly: 200442-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director 
Valves:   707150-5 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
Valves:   707150-6 1 Task Master III™ 1 1/2" or 2" SS Control Valve with indicator light (slave unit) 
Super flow kit: 720002 2 2" Super flow kit with two DM200G cast iron diaphragm valves
Tank Adaptor: 720216 2 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 500841 1  PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm
Dimensions (HtxDepthxWidth):  DIMMF150T - 69 ¼” x 31 ¼” x 76” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150T - 1661 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- TA - Twin Alternating (- TA).  In twin alternating (TA) mode units operate so that once a predetermined amount of water has passed through the flow meter the ERCd initiates regeneration of the exhausted unit placing its twin in service. One unit is on line (in service) and one is either in standby or regeneration. The ERCd demand initiated regeneration controller controls the regeneration cycles for both of the twin alternating units in a master slave configuration. Twin alternating systems shall have two mineral tanks, two Taskmaster IIIä control valves, one brine tank with brine director, one ERCd controller, one PW, PWS or TM series flow meter and two shut off kits. Regeneration initiation and meter display shall be provided by the ERCd.
Optional PG & test tap kit: PGTTK 2 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 921152-12   Model MF-150-2"-TP Twin Parallel Water Softener 
       
Mineral Tank:  100123-LC 2 20x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels
Upper distributor: 100341 2 2" Single point upper SCH80PVC
Lower distributor: 500000-1 2 Two point - 2" lower SCH80PVC
Face Piping: 809606 2 2" & 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW10 2 10 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479922 2 5 ft³ / 100 lb  per vessel
Rated continuous /  peak flow: QMF150T2 - 50 / 75 gpm per vessel  :  100 / 150 gpm both vessels
Capacity: CAPMF150T - 153,000 grains per vessel : 306,000 grains both vessels
Brine Tank:  805076 1 24X40 Accumatic™ Brine System 16" Grid Ht
Brine Draw: 66 lbs Salt Storage 500 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Director Assembly: 200442-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 3/4" Brine Director 
Valves:   707150-5 2 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
- * - -
Super flow kit: 720002 2 2" Super flow kit with two DM200G cast iron diaphragm valves
Tank Adaptor: 720216 2 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 500841 2  PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm
Dimensions (HtxDepthxWidth):  DIMMF150T - 69 ¼” x 31 ¼” x 76” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF150T - 1661 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- TP - Twin Parallel (–TP) systems are demand regenerated. Each tank is controlled independently by a separate controller (ERCd). For each mineral vessel, the separate controllers determine if the resin in the mineral tank is exhausted based on the volume of water treated (or totalized flow) and then signals the cycle timer to regenerate that particular vessel. The vessels operate independently. Simultaneous regeneration is controlled by blocking regeneration based on time of day. The two units operate completely independently resulting in a truly redundant system. 
Optional PG & test tap kit: PGTTK 2 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 920240   Model MF-240-1 ½”-Simplex (SX) Water Softener 
       
Mineral Tank:  100124-LC 1 24x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels 
Upper distributor: 100341 1 2" Single point upper SCH80PVC
Lower distributor: 500000-1 1 Two point - 2" lower SCH80PVC
Face Piping: 806603 1 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW15 1 15 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479926 1 8 ft³ / 150 lb  per vessel
Rated continuous /  peak flow: QMF240S1 - 51 / 67 gpm per vessel 
Capacity: CAPMF240S - 245,000 grains per vessel
Brine Tank:  805077 1 24X50 Accumatic™ Brine System 21" Grid Ht
Preset Brine Draw: 91 lbs Salt Storage 640 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Line Assembly: 200126-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 
Valves:   707150 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCt 99-day electronic timer 
- * - -
Bypass: BYPASS - Unit will bypass hard water during regeneration
Tank Adaptor: 720216 1 Taskmaster III Side Mount SS Tank Adaptor
- * - -
Dimensions (HtxDepthxWidth):  DIMMF240S - 70 1/2” x 35 ¼” x 54” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF240S - 1111 lbs
Literature: LITMF - CAT231, CAT315, CAT281, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
Operating Mode: SIMPLEX - Simplex (-SX). Simplex systems shall have regeneration initiated by time of day or “clock time”. SX systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCt controller. Ordering an optional shut off kit will prevent hard water bypass.
Optional PG & test tap kit: PGTTK 1 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 920240-5   Model MF-240-1 ½”-Simplex Metered (SM) Water Softener 
       
Mineral Tank:  100124-LC 1 24x54 Carbon steel, epoxy lined and coated, 100-psi, non-code vessels 
Upper distributor: 100341 1 2" Single point upper SCH80PVC
Lower distributor: 500000-1 1 Two point - 2" lower SCH80PVC
Face Piping: 806603 1 1 ½” NPT and grooved galvanized face piping
Backwash Rate: BW15 1 15 gpm internal BW control
with 3/4" drain
Media (Resin / gravel):  479926 1 8 ft³ / 150 lb  per vessel
Rated continuous /  peak flow: QMF240S1 - 51 / 67 gpm per vessel 
Capacity: CAPMF240S - 245,000 grains per vessel
Brine Tank:  805077 1 24X50 Accumatic™ Brine System 21" Grid Ht
Preset Brine Draw: 91 lbs Salt Storage 640 lbs
Brine Valve: 706022 1 ⅜” Brine Valve
Brine Line Assembly: 200126-2 1 ½” Poly Propylene Tubing for ⅜” Brine Valve 
Valves:   707150-5 1 Task Master III™ 1 1/2" or 2" SS Control Valve with ERCd demand regeneration control 
- * - -
Bypass: BYPASS - Unit will bypass hard water during regeneration
Tank Adaptor: 720216 1 Taskmaster III Side Mount SS Tank Adaptor
Flow Meter: 500841 1  PW150 1 ½” Paddle Wheel Flow Meter  5-140 gpm
Dimensions (HtxDepthxWidth):  DIMMF240S - 70 1/2” x 35 ¼” x 54” 
- ADD - Add one foot to height for loading media.
Shipping Weight: WTMF240S - 1111 lbs
Literature: LITMFMTR - CAT231, CAT315, CAT370, CAT281, CAT420, CAT610, O&M No 900401
Conditions: OPCOND - Max Operating Temp: 120F Max Operating Pressure: 125 psi
- * - -
- SIMPLEX MTR - Simplex metered (-SM). Simplex metered systems shall have regeneration initiated by gallons treated (demand). SM systems shall have one brine tank, one Taskmaster IIIä control valve, one ERCd controller, one PW, PWS or TM series flow meter. Regeneration initiation and meter display shall be provided by the ERCd. This unit will bypass hard water during regeneration.
Optional PG & test tap kit: PGTTK 1 Two 2 ½” Ø face oil filled PGs and brass sample valve (720075-4) per vessel

 

 BACK TO TOP

Part No Quant Description
System: 920242-10