Part Number:
930572-11
System Type:
Twin Alternating
Pipe Size: 2”
PVC Solvent Weld
Valve /
Controller: Two (2) Magnum IT 2" 962 Conditioner Controller EDC, 60
HZ, TA, Internal Turbine Meter, Battery Backup Capable, No Untreated Water
Bypass, Includes 120 VAC Transformer
Bypass Piping: Two
(2) Magnum Cv™ PLUS Adapter Kits – Brass 1 ½” NPT for Inlet, Outlet, and
Drain
Meter:
Internal TM200
Mineral Tank: Two (2) 24” x 72”
Composite Fiberglass Mineral Vessels w/4” Threaded Top Opening & Skirt Style
Base
Distributor:
Single point SCH80PVC
Media (Resin /
gravel): 8 ft³ / 200 lb (479907) per vessel
Brine
Injector: Internal
Brine Tank:
24X50 Accumatic™ Brine System (805077)
Brine Valve:
3/8” (706022)
Brine Director
Assembly: 1/2” (200442-2)
Preset brine
draw: 106 lbs
Salt Storage:
580 lbs
Continuous / Peak
Flow: 61/81 gpm per tank
Backwash
Rate: 15 gpm
Factory Preset
Capacity: 245,000 grains per tank
Low to High Salt
Range: 160 to 246 Kgr per tank
System
Capacity: 480 Kgr
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
78” x 24” x 84” (add one foot to height for loading media)
Shipping
Weight: 1355 lbs
O & M
Manuals: 3 included with system
PGTTK: One
(1) Set 2½” Stainless Steel Liquid Filled Pressure Gauges (0-160) and Brass
Test Tap Kit (Inlet/Outlet) per Vessel
Model BF-300-2-Twin Parallel Water Softener
Part
Number: 930573-11
System Type:
Twin Parallel
Pipe Size:
2” PVC Solvent Weld
Valve /
Controller: Two (2) Taskmaster IV 2" Conditioner Controller with
ARCT Timer, 60 HZ. No Untreated Water Bypass, Includes 120 VAC
Transformer, rated at 25 – 100 psi working pressure, 35º - 100º F water
temperature
Control:
Two - EDR II™ (800130-1 ½) with ARCT timers.
Meter: Two – PW150 1 ½” Paddle wheel flow meters.
Mineral Tank: Two (2) 30” x 72”
Composite Fiberglass Mineral Vessels w/4” Threaded Top Opening & Skirt
Style Base rated at 150 psi working pressure and 150º F water temperature
Distributor: Hub and Lateral Plastic
Media (Resin /
gravel): 10 ft³ / 250 lb (479908) per vessel
Brine
Injector: Internal
Brine Tank:
24X50 Accumatic™ Brine System (805077)
Brine Valve:
¾” (706054)
Brine Line
Assembly: ¾” (200442-2)
Preset brine
draw: 106 lbs
Salt
Storage: 580 lbs
Continuous /
Peak Flow: 76/89 gpm per tank
System Cont /
Peak Flow: 150/178 gpm per tank
Backwash
Rate: 25 gpm
Factory Preset
Capacity: 293,000 grains per tank
Low to High Salt
Range: 200 to 310 Kgr per tank
System
Capacity: 586 Kgr
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
82” x 30” x 96” (add one foot to height for loading media)
Shipping
Weight: 2090 lbs
O & M
Manuals: 3 included with system
Model BF-300-2-Twin Alternating Water Softener
Part
Number: 930573-11
System Type:
Twin Alternating
Pipe Size:
2” PVC Solvent Weld
Valve /
Controller: Two (2) Magnum IT 2" 962 Conditioner Controller EDC, 60
HZ, TA, Internal Turbine Meter, Battery Backup Capable, No Untreated Water
Bypass, Includes 120 VAC Transformer, rated at 25 – 100 psi working
pressure, 35º - 100º F water temperature
Bypass Piping:
Two (2) Magnum IT™ with 2” NPT for Inlet, Outlet, and 1 ½” NPT Drain
Meter:
Internal TM200
Mineral Tank: Two (2) 30” x 72”
Composite Fiberglass Mineral Vessels w/4” Threaded Top Opening & Skirt
Style Base rated at 150 psi working pressure and 150º F water temperature
Distributor: Hub and Lateral Plastic
Media (Resin /
gravel): 10 ft³ / 250 lb (479908) per vessel
Brine
Injector: Internal
Brine Tank:
24X50 Accumatic™ Brine System (805077)
Brine Valve:
¾” (706054)
Brine Line
Assembly: ¾” (200442-2)
Preset brine
draw: 106 lbs
Salt
Storage: 580 lbs
Continuous /
Peak Flow: 76/89 gpm per tank
Backwash
Rate: 25 gpm
Factory Preset
Capacity: 293,000 grains per tank
Low to High Salt
Range: 200 to 310 Kgr per tank
System
Capacity: 586 Kgr
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
82” x 30” x 96” (add one foot to height for loading media)
Shipping
Weight: 2090 lbs
O & M
Manuals: 3 included with system
PGTTK: One
(1) Set 2½” Stainless Steel Liquid Filled Pressure Gauges (0-160) and
Brass Test Tap Kit (Inlet/Outlet) per Vessel (720075-4)
Model BF-450-2-Simplex Water Softener
Part
Number: 930576
System Type:
Simplex
Pipe Size:
2” PVC Solvent Weld
Valve /
Controller: One (1) Magnum IT 2" with 942 6 or 7 day controller. 60
HZ, Battery Backup Capable, with Untreated Water Bypass, Includes 120 VAC
Transformer
Mineral Tank: One (1) 36” x 72”
Composite Fiberglass Mineral Vessels w/4” Threaded Top Opening & Skirt
Style Base
Distributor: Hub and lateral – Plastic
Media (Resin /
gravel): 15 ft³ / 300 lb (479909) per vessel
Brine
Injector: Internal
Brine Tank:
30X50 Accumatic™ Brine System (805177)
Brine Valve:
1/2” (706044)
Brine Line
Assembly: 1/2” (200126-3)
Preset brine
draw: 145 lbs
Salt
Storage: 900 lbs
Continuous /
Peak Flow: 61/81 gpm per tank
Backwash
Rate: 35 gpm
Factory Preset
Capacity: 432,000 grains per tank
Low to High Salt
Range: 300 to 480 Kgr per tank
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
96” x 36” x 72” (add one foot to height for loading media)
Shipping
Weight: 1385 lbs
O & M
Manuals: 3 included with system
PGTTK: One
(1) Set 2½” Stainless Steel Liquid Filled Pressure Gauges (0-160) and
Brass Test Tap Kit (Inlet/Outlet) per Vessel
Part
Number: 930578-11
System Type:
Twin Alternating
Pipe Size:
2” PVC Solvent Weld
Valve /
Controller: Two (2) Magnum IT 2" 962 Conditioner Controller EDC, 60
HZ, TA, Internal Turbine Meter, Battery Backup Capable, No Untreated Water
Bypass, Includes 120 VAC Transformer, rated at 25 – 100 psi working
pressure, 35º - 100º F water temperature
Bypass Piping:
Two (2) Magnum IT™ with 2” NPT for Inlet, Outlet, and 1 ½” NPT Drain
Meter:
Internal TM200
Mineral Tank: Two (2) 36” x 72”
Polyglass Mineral Tanks
Distributor: Hub and Lateral Plastic
Media (Resin /
gravel): 20 ft³ / 300 lb (479910) per vessel
Brine
Injector: Internal
Brine Tank:
39X60 Accumatic™ Brine System (805178)
Brine Valve:
¾” (706054)
Brine Line
Assembly: ¾” (200442-2)
Preset brine
draw: 244 lbs
Salt
Storage: 2,000 lbs
Continuous /
Peak Flow: 71/94 gpm per tank
Backwash
Rate: 35 gpm
Factory Preset
Capacity: 594,000 grains per tank
Low to High Salt
Range: 400 to 620 Kgr per tank
System
Capacity: 1,118 Kgr
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
82” x 30” x 96” (add one foot to height for loading media)
Shipping
Weight: 2825 lbs
O & M
Manuals: 3 included with system
Model BF-720-2-Twin Alternating Water Softener
Part Number:
CP-930578-11
System Type:
Twin Alternating
Pipe Size: 2”
PVC Solvent Weld
Valve /
Controller: Two (2) Magnum IT 2" with ERCd Conditioner Controller, 60
HZ, TA, Internal Turbine Meter, Battery Backup Capable, No Untreated Water
Bypass, Includes 120 VAC Transformer, rated at 25 – 100 psi working
pressure, 35º - 100º F water temperature
Shut-Off-Kit: None
Meter:
Internal TM200
Mineral Tank: Two (2) 36” x 72”
Polyglass Mineral Tanks
Distributor:
Hub and Lateral Plastic
Media (Resin /
gravel): 24 ft³ / 300 lb (479910-1) per vessel
Brine
Injector: Internal
Brine Tank:
39X60 Accumatic™ Brine System (805178)
Brine Valve:
¾” (706054)
Brine Line
Assembly: ¾” (200442-2)
Preset brine
draw: 244 lbs
Salt Storage:
2,000 lbs
Continuous / Peak
Flow: 71/94 gpm per tank
Backwash
Rate: 35 gpm
Factory Preset
Capacity: 594,000 grains per tank
Low to High Salt
Range: 400 to 620 Kgr per tank
System
Capacity: 1,118 Kgr
System includes
polyethylene loading funnel.
Dimensions (HtxDepthxWidth):
82” x 30” x 96” (add one foot to height for loading media)
Shipping
Weight: 2825 lbs
O & M
Manuals: 3 included with system
Twin alternating
units operate so that once a predetermined amount of water has passed
through the flow meter the ERCd initiates regeneration of the exhausted unit
placing its twin in service. One unit is on line and one is either in
standby or service. The ERCd demand initiated regeneration controller
controls the regeneration cycles for both of the twin alternating units. TA
systems shall have two mineral tanks, two Magnum ITä
control valves (a primary with EDRd and a secondary), one brine tank with
brine director, one PW, PWS or TM series flow meter and two shut off kits.
Regeneration initiation and meter display shall be provided by the ERCd.